OPTO 22 - GRV-CSERI-4 _ Serial communication, 4 channels, RS-232 or RS-485, channel-to-channel isolation
Write a Review
OPTO 22
OPTO 22 - GRV-CSERI-4 _ Serial communication, 4 channels, RS-232 or RS-485, channel-to-channel isolation
- Brand
- OPTO 22
- SKU:
- GRV-CSERI-4
- UPC:
OPTO 22 - GRV-CSERI-4 _ Serial communication, 4 channels, RS-232 or RS-485, channel-to-channel isolation
Quick Specs:
- Serial communication
- 4 channels
OPTO 22 - GRV-CSERI-4 _ Serial communication, 4 channels, RS-232 or RS-485, channel-to-channel isolation
Quick Specs:
- Serial communication
- 4 channels
- RS-232 or RS-485
- channel-to-channel isolation
The GRV-CSERI-4 serial communication module provides 4 independent, isolated serial ports for communication with RS-232 or RS-485 serial devices. The module can communicate with RS-485 serial devices in half-duplex (2-wire transmission) or full-duplex (4-wire transmission) mode.
Each port is selectable between RS-232 and RS-485, with configurable termination and bias in RS-485 mode. Port 0 can also be configured to handle modem commands. Baud rates of up to 1 Mbps are supported.
Part of the groov ® EPIC system, the GRV-CSERI-4 mounts on any groov EPIC® chassis alongside a GRV-EPIC-PR1 processor and analog and discrete groov I/O modules, to provide the mix of signals you need at any location.
groov serial modules are directly connected to the processor via the bus on the chassis, so each serial port works like a port that's built into the processor. groov serial modules contain two to four ports, and serial modules can be placed in any of the first four positions on the chassis; so depending on the serial modules you use, you can add up to 8 to 16 serial ports to your GRV-EPIC-PR1.
Note that this direct connection means that an EPIC processor can control serial modules on its own chassis, but it cannot control serial modules on a separate EPIC chassis. Other devices, such as a SNAP PAC controller, also cannot control serial modules on an EPIC chassis.
Note: This module requires groov EPIC Firmware 1.2.0 or higher on your GRV-EPIC-PR1.
Specifications:
Feature | Port 0 | Port 1 | Port 2 | Port 3 |
RS-232 Tx / Rx | x | x | x | x |
RS-232 RTS / CTS | x | x | x | x |
RS-232 DCD, DTR, DSR, RI | x | |||
RS-485 half-duplex mode (TxRx+/-) | x | x | x | x |
RS-485 full-duplex Mode (Tx+/-, Rx+/-) | x | x | x | x |
RS-485 termination (120 Ohms) | x | x | x | x |
RS-485 Bias (750 Ohms to +V and COM) | x | x | x | x |
Specification | GRV-CSERI-4 | |||
Serial Standards | RS-232 (DTE), RS-485 half and full duplex | |||
Baud Rates | 300 bps - 1 Mbps | |||
Maximum Cable Length (RS-232) | 10 m | |||
Maximum Cable Length (RS-485) | 1200 m at 38.4 Kbps, 500 m at 115.2 Kbps, 50 m at 1 Mbps | |||
Bus Loading (RS-485) | 1/8 Unit Load | |||
Bus Termination | 5 KOhms (RS-232 mode), 120 Ohms (RS-485 mode, selectable) | |||
Bus Bias | 750 Ohms, (RS-485 mode only, selectable) | |||
Isolation (field-to-logic) | 300 V working, 1500 V transient (1 minute) | |||
Isolation (channel-to-channel) | 300 V working | |||
Number of Channels | 4 individually configurable channels | |||
Indicators | Transmit and Receive LEDs for each channel | |||
Chassis Power Consumption | 1.5 W | |||
Chassis Compatibility | Slots 0-3 only. The maximum number of modules per chassis is 4. | |||
Minimum GRV-EPIC-PR1 Firmware Version | 1.2.0 | |||
Wire Size | 28 - 14 AWG | |||
Torque, connector screw | 2.5 in-lb (0.28 N-m) | |||
Torque, hold-down screw | 3.5 in-lb (0.4 N-m) | |||
Temperature (operating) | -20 °C to +70 °C | |||
Temperature (storage) | -40 °C to +85 °C | |||
Relative Humidity (non-condensing) | 5 - 95% | |||
Agency Approvals | UL/cUL (Class 1 Div. 2)a; CE, ATEX (Category 3, Zone 2), RoHS; DFARS; CB Scheme; UKCA | |||
Warranty | 30 months | |||
a For use in hazardous locations, equipment must be mounted in an enclosure that meets the requirements of the National Electrical Code, ANSI/NFPA 70, and ANSI/ISA-61010-1 (82.02.01). |
0 Reviews Hide Reviews Show Reviews
OPTO 22
OPTO 22 - GRV-CCANI-2 _ Serial communication, 2 channels, CAN, channel to channel isolation
OPTO 22
OPTO 22 - GRV-ITMI-8 _ Analog input, 8 channel, thermocouple or mV, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-IACIHV-12 _ AC input, 12 channels, 180-280 VAC, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-IDCI-12 _ DC digital input, 12 channels, 10-30 V, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-ODCI-12 _ DC digital output, 12 channels, 5-60 VDC, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-OACI-12 _ AC digital output, 12 channels, 12-250 VAC, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-IACI-12 _ AC digital input, 12 channels, 85-140 VAC, channel-to-channel isolation
OPTO 22
OPTO 22 - SNAP-SCM-232 _ SNAP 2-Ch RS-232 Serial Communication Module
OPTO 22