Quick Specs:
- AC/DC output
- 8 channels
- electromechanical relay
- 0-250 VAC/5-30 VDC
- 5 A
The GRV-OMRIS-8 is a mechanical relay output module that offers 8 channels for switching loads of up to 5 amps at 250 VAC or 30 VDC. These are form C relays, so each of the 8 mechanical relays can be wired as normally open or normally closed. Fusing is not provided; you must provide fusing when wiring the module.
Part of the groov EPIC® system, the GRV-OMRIS-8 can mechanically switch either AC or DC loads, potentially reducing the number of modules needed. Its 8 channels are all isolated from each other (channel-to-channel isolation). The module offers little or no leakage current when the contacts are open and is suitable for piloting electronic coil contactors.
The GRV-OMRIS-8 module mounts on a groov EPIC chassis with a GRV-EPIC-PR1 processor and a variety of groov I/O modules (analog, discrete, and serial) to suit your application needs.
Part of the groov EPIC® system, the GRV-OMRIS-8 can mechanically switch either AC or DC loads, potentially reducing the number of modules needed. Its 8 channels are all isolated from each other (channel-to-channel isolation). The module offers little or no leakage current when the contacts are open and is suitable for piloting electronic coil contactors.
The GRV-OMRIS-8 module mounts on a groov EPIC chassis with a GRV-EPIC-PR1 processor and a variety of groov I/O modules (analog, discrete, and serial) to suit your application needs.
Specifications:
Specification | GRV-OMRIS-8 | |||
Line Voltage Range (nominal) | 0 - 250 VAC or 5 - 30 VDC | |||
Current Rating | 5 A per channel | |||
Surge Current | 6 A peak for 1 second | |||
Recommended Fuse / Circuit Breaker | 5 A at 250 VAC / > 30 VDC per channel | |||
Leakage Current | < 2 µA @ 250 VAC | |||
Contact Resistance | ¤100 mOhms | |||
Turn-On Time | 8 ms | |||
Turn-Off Time | 4 ms | |||
Operating Life (to specification) | Min. 30,000 cycles at max. ratings | |||
Mechanical Life | Min. 10,000,000 cycles | |||
Transient Clamp Holding Voltage | 440 V | |||
Transient Clamping Voltage (max.) | 720 V | |||
Isolation (coil-to-contact) | 4000 VACrms 1 min., 10 mA detect/channel | |||
Isolation (channel-to-channel) | 300 VAC operating, 1500 Vrms max. | |||
Number of Channels | 8 | |||
Chassis Power Consumption | 1.4 W | |||
Wire Size | 28 - 14 AWG | |||
Torque, connector screw | 2.5 in-lb (0.28 N-m) | |||
Torque, hold-down screw | 3.5 in-lb (0.4 N-m) | |||
Temperature (operating) | -20 °C to +70 °C | |||
Temperature (storage) | -40 °C to +85 °C | |||
Shock (misoperation) | 5 G | |||
Shock (survival) | 100 G | |||
Relative Humidity (non-condensing) | 5 - 95% | |||
Agency Approvals | UL/cUL (Class 1 Div. 2)a; CE, ATEX (Category 3, Zone 2), RoHS; DFARS; CB Scheme; UKCA | |||
Warranty | 30 months | |||
a For use in hazardous locations, equipment must be mounted in an enclosure that meets the requirements of the National Electrical Code, ANSI/NFPA 70, and ANSI/ISA-61010-1 (82.02.01). |