OPTO 22 - GRV-IV-24 _ Analog voltage input, 24 channels, 8 configurable input ranges from +/-160 V to +/-1.25 V
- Brand
- OPTO 22
- SKU:
- GRV-IV-24
OPTO 22 - GRV-IV-24 _ Analog voltage input, 24 channels, 8 configurable input ranges from +/-160 V to +/-1.25 V
Quick Specs:
- Analog voltage input
- 24 channels
- 8 configurable input ranges from +/-160 V to +/-1.25 V
- ±160.0 VDC
- ±80.0 VDC
- ±40.0 VDC
- ±20.0 VDC
- ±10.0 VDC
- ±5.0 VDC
- ±2.5 VDC
- ±1.25 VDC
Part of the groov EPIC® system, the GRV-IV-24 module mounts on a groov EPIC chassis together with a GRV-EPIC-PR1 processor and other analog, discrete, and serial groov I/O modules.
Specifications:
Features | GRV-IV-24 | GRV-IVI-12 | GRV-IVIRMS-10 |
---|---|---|---|
Scaling | x | x | x |
Offset and Gain | x | x | x |
Minimum/Maximum Values | x | x | x |
Average Filter Weight | x | x | x |
Simple Moving Average | x | x | x |
Analog Totalizing | x | x | x |
Problem Indication | x | x | x |
Specification | GRV-IV-24 | GRV-IVI-12 | GRV-IVIRMS-10 | |
---|---|---|---|---|
Input Ranges | ±160.0 VDC ±80.0 VDC | ±160.0 VDC ±80.0 VDC | 300.0 V rmsAC/DC 150.0 V rms AC/DC | |
Over-range limits | ±176.0 VDC ±88.0 VDC | ±176.0 VDC ±88.0 VDC | 333.0 V rms AC/DC 165.0 V rms AC/DC | |
Resolution | Range / 1,048,576 (20-bits) | Range / 1,048,576 (20-bits) | Range / 1,048,576 (20-bits) | |
Accuracy 0.1% of Range | ±160 mV ±80 mV ±40 mV | ±160 mV ±80 mV ±40 mV | N/A | |
Accuracy @ 50-60 Hz | N/A | N/A | ±200 mV and ±0.2% of reading | |
Accuracy @ 60-400 Hz | N/A | N/A | ±200 mV and ±0.3% of reading | |
Input Impedance Nominal | 9.7 megohms | 9.7 megohms | 9.5 megohms | |
Input Filter | -3 dB at 46 HZ | -3 dB at 46 HZ | N/A | |
DC Reversal | N/A | N/A | 1% of Range | |
Software Data Filtering:
|
|
|
| |
Step Input Response Time | 512 ms x SMA value Default SMA: 4 | 16.5 ms x SMA value Default SMA: 4 |
| |
Data Refresh Time | 512 ms | 15.5 ms | 50 ms | |
Analog Data Filtering | -3 dB @ 2.4 Hz | -3 dB @ 46 Hz | N/A | |
Common Mode Rejection | > -120 dB | > -120 dB | > -120 dB | |
Max. Survivable Input | 300 V | 300 V | 330 V | |
Max. Operating Common | 250 V | 250 V | 300 V | |
Problem Indications | out of range | out of range | out of range | |
Isolation (field-to-logic) | 300 V working, | 300 V working, | 300 V working, | |
Isolation (channel-to-channel) | 300 V between | 300 V working, | 300V working, | |
Number of Channels | 24 | 12 | 10 | |
Chassis Power Consumption | 1.0 W | 2.2 W | 1.5 W | |
Minimum GRV-EPIC-PR1 | 1.0.0 | 1.4.2 | 1.5.0 | |
Minimum PAC Project Version | 10.0000 | 10.2003 | 10.2005 | |
Minimum Library Package for CODESYS Version | 1.0.0.0 | 1.0.2.0 | 1.0.3.0 | |
Wire Size | 28-14 AWG | 28-14 AWG | 28-14 AWG | |
Torque, connector screw | 2.5 in-lb (0.28 N-m) | 2.5 in-lb (0.28 N-m) | 2.5 in-lb (0.28 N-m) | |
Torque, hold-down screw | 3.5 in-lb (0.4 N-m) | 3.5 in-lb (0.4 N-m) | 3.5 in-lb (0.4 N-m) | |
Temperature (operating) | -20 °C to +70 °C | -20 °C to +70 °C | -20 °C to +70 °C | |
Temperature (storage) | -40 °C to +85 °C | -40 °C to +85 °C | -40 °C to +85 °C | |
Relative Humidity | 5-95% | 5-95% | 5-95% | |
Agency Approvals | UL/cUL (Class 1 Div. 2)a; CE, ATEX (Category 3, Zone 2), RoHS; DFARS; CB Scheme; UKCA | |||
Warranty | Lifetime | Lifetime | Lifetime | |
a For use in hazardous locations, equipment must be mounted in an enclosure that meets the requirements of the National Electrical Code, ANSI/NFPA 70, and ANSI/ISA-61010-1 (82.02.01). |