OPTO 22 - G4IDC5-SWNC _ G4 DC Input - DC voltage, self-powered, normally closed
- Brand
- OPTO 22
- SKU:
- G4IDC5-SWNC
OPTO 22 - G4IDC5-SWNC _ G4 DC Input - DC voltage, self-powered, normally closed
Quick Specs:
- G4 DC Input - DC voltage
- self-powered
- normally closed
The G4IDC5-SWNC module provides one isolated channel of contact status input, sensing switch opening. The module supplies 15 volts of power to an external dry contact switch.
Each user-supplied switch is connected with two wires. Because these modules include power for the switch, this module is particularly cost-effective when labor costs for wiring external power are high.
Typical applications for the G4IDC5-SWNC include sensing contact opening from sources such as switched status sensors (level sensors, pressure indicators, etc.), magnetic reed switches (used on doors or windows for burglar alarms), snap-action micro switches, the auxiliary switches on motor starters, and most relay contacts.
CAUTION: G4IDC5-SW and G4IDC5-SWNC inputs are not intended to be used with contacts that are connected to any external user-supplied voltage or current.
Specifications:
Field Side Ratings | |
Open Circuit Voltage (Switch Open) | 11 VDC min., 13 VDC typical, 15 VDC max. |
Short Circuit Current (Switch Closed) | 6 milliamps nominal |
Minimum Off Resistance | ¥20 K ohms |
Maximum Allowable On Resistance | 500 ohms |
Logic Side Ratings | |
Logic Output Voltage for G4IDC5-SW | <0.5 V max. (switch closed; LED on) @ 2 mA sinking |
Logic Output Voltage for G4IDC5-SWNC | <0.5 V max. (switch open; LED on) @ 2 mA sinking |
Maximum Operating Common Mode | 250 V |
Power Requirements: | 5 VDC (±0.25) @ 25 mA nom. |
Module Ratings | |
Number of Channels Per Module | 1 |
Turn-on Time | 8 msec typical |
Turn-off Time | 8 msec typical |
Input-to-output Isolation (transient) | 4000 V AC/DC |
Temperature | 0 °C to 70 °C, operating |