Quick Specs:
Quick Specs:
The AD11T analog input module provides a single channel of optically isolated and channel-to-channel isolated voltage-to-digital conversion. Nominal voltage input is -5 to +5 VDC. The module's 4,000 Vrms channel-to-channel isolation eliminates ground loop problems.
This module mounts on a G1 analog mounting rack, for example the PB16AH.
| AD11T | |||
---|---|---|---|---|
Nominal Voltage Input | -5 to + 5 VDC | |||
Over/Under Range Capability | -5.25 to 11 VDC | |||
Accuracy* | ± 10 mV | |||
Power Requirements | 15 mA at +15 (+/- 0.25) VDC | |||
Input Response Time | 5% of scale change in 8.5 ms 63% of scale change in 165 ms | |||
Resolution | 12-bits | |||
Isolation | 4,000 VRMS | |||
Temperature | 0 to 70 °C | |||
Agency Approvals | CE; RoHS; UKCA | |||
*May be improved by the use of the "Set Offset" or "Set Gain" commands in the OPTOMUX command set. |