Quick Specs:
Quick Specs:
The AD10T2 is a 100 ohm platinum RTD analog input with a nominal temperature range of -50 °C to 350 °C (-58 °F to 662 °F). This module provides a single channel of optically isolated RTD temperature-to-digital conversion with 4,000 Vrms of transient isolation.
This module is suitable for temperature measurements where the RTD probe is grounded or when ground loop currents exist.
| AD10T2 | AD14T |
RTD Input | 100 é platinum (ñ = 0.00385) | 10 é copper |
Nominal Temperature Range | - 50 °C to 350 °C | - 55 °C to 150 °C |
Nominal Temperature Range | - 58 °F to 662 °F | - 67 °F to 302 °F |
Over/Under Range | - 60 °C to 812 °C | N/A |
Over/Under Range | - 140 °F to 1493 °F | N/A |
Accuracy | ± 0.4 °C | ± 0.6 °C |
Resolution | 12 bits | 12 bits |
Response Time | full scale step change in 100 ms | full scale step change in 100 ms |
Isolation Transient | 4,000 VRMS | 4,000 VRMS |
Power Requirements | 45 mA at +15 (+/- 0.25) VDC and 45 mA at -15 (+/- 0.25) VDC | 35 mA at +15 (+/- 0.25) VDC and 35 mA at -15 (+/- 0.25) VDC |
Temperature | 0 °C to 70 °C | 0 °C to 70 °C |
Agency Approvals | CE; RoHS; UKCA | CE; RoHS; UKCA |
OPTO 22
OPTO 22
OPTO 22
OPTO 22
OPTO 22