Crompton PTG5-2-110-1442 _ Medium Voltage Potential Transformer s, Two Bushing, Unfused, Primary Voltage - 14400
$1,337.77
- Brand
- Crompton
- SKU:
- PTG5-2-110-1442
- Availability:
- Y
Crompton PTG5-2-110-1442 _ Medium Voltage Potential Transformer s, Two Bushing, Unfused, Primary Voltage - 14400
ACCURACY CLASS:
0.3 WXMYZ, 1.2ZZ at 100% rated voltage with 120V based ANSI burden; 0.3 WXMY, 1.2Z at 58% rated voltage with 69.3V based ANSI burden
FREQUENCY:
60 Hz.
MAXIMUM SYSTEM VOLTAGE:
15.5kV, BIL 110kV full wave
THERMAL RATING:
1500 VA at 30°C. amb.
1000 VA at 55°C. amb.
APPROXIMATE WEIGHT:
85 lbs., unfused
Features:
- Primary terminals that are unfused are¼ - 20 brass screws with one flat washer and lockwasher, unless otherwise specified.
- Primary terminals that are fused are¼ - 20 brass screws with one flat washer, lockwasher and two nuts.
- Secondary terminals are No. 10-32 brass screws with one flat washer and lockwasher.
- The core and coil assembly is vacuum encapsulated in polyurethane resin.
- Thermal burden rating is for 120 volt secondaries
- Plated steel Mount ing base.
- Fuses have 1.63" Dia Caps and 11.50" clip centers.
- Switchgear style is similar to fused style. No fuse or fuse clip is provided, but inserts for fuse clips are supplied.
- A test cord is provided with each unit.
Specifications:
- Catalog Number: PTG5-2-110-1442
- Group: 2
- Primary Voltage: 14400
- Ratio: 120:1
- Secondary Voltage: 120
- Type: Unfused