Crompton 467-600 _ Voltage Transformer , Turns Ratio - 5:1, Voltage Rating - 600:120
$274.02
- Brand
- Crompton
- SKU:
- 467-600
- Availability:
- Y
Crompton 467-600 _ Voltage Transformer , Turns Ratio - 5:1, Voltage Rating - 600:120
FREQUENCY:
60 Hz.
STANDARD SECONDARY VOLTAGE:
120 Volts
INSULATION LEVEL:
600 Volts. 10 kV BIL. full wave
ACCURACY CLASS:
± 1% at all burdens up to 5 VA at 1.0 and 0.95 P.F.
THERMAL RATING:
40 VA AT 30°c . amb, 27 VA AT 55°c. amb
APPROXIMATE WEIGHT:
2.5 lbs.
CONNECTIONS:
-Terminals are No. 6-32 screws with one lockwasher and one flat washer
Features:
- The core and coil assembly is encased in a thermoplastic shell and filled with resin.
- Each Transformer has a clear plastic terminal cover.
- These Transformer s are designed for operation line to line. They may also be operated line to ground or line to neutral at reduced voltage (58% of rated volts).
- It is desirable to use a 0.40 amp fuse in the secondary to protect the Transformer .
- Models designed specifically for 50Hz operation are available with reduced performance consult factory for details.
Specifications:
- Catalog Number: 467-600
- Voltage Rating: 600:120
- Turns Ratio: 5:1
- Rec. Primary Fuse Rating: 0.25
- Weight in lbs: 2.5
Specifications Sheet: