Yokogawa 30031A _ Clamp-on Tester Leakage CurrentThe 30031A and 30032A are small leakage current clamp meters by Yokogawa. The 30031A Clamp-On Leakage Current Tester has a sharp low pass filter function, and the 30032A Clamp-On Current Leakage Tester is capable of measuring from 1 mA AC. Both models of leakage current test equipment use mean value as their leakage current measurement method of detection and rms value calibration.
See Yokogawa's Leakage Current Test Equipment Brochure and both models' instruction manuals for complete details on measuring leakage current.
Specifications:
Specifications
Description | Leakage Current Mini Clamp-on; 3/30mA/30/60 Amp |
---|---|
Method of detection | Mean Value |
Display | (Bar-graph display: 32 segments) LCD (Digital display: 3200 counts) |
Range Switching | Auto-range |
Operating temperature and humidity | 0 - 50°, 80% RH or less (no condensation) |
Influence of external magnetic field | 0.0005% typical 1 (on current value of adjacent cable) |
Influence of conductor position | Within accuracy |
Safety Standard | Approved for conformity to EN 61010-1,EN 61010-2-032 |
Circuit voltage | 300 Vrms or less |
Withstanding voltage | 3.7 kV AC for one minute |
Power Supply | One CR2032 (Coin-shaped) 3 V battery |
Battery Life | Approx. 90 hours (when continuously used) |
Auto power-off | Approx. 10 minutes |
Diameter of measurable conductor | 40 at maximum mm |
Dimensions | Approx. 70 (W) x 176 (H) x 25 (D) mm |
Weight | Approx. 200 g |
Accessories | Instruction manual, battery, Soft case |
AC Current | 3/30 mA, 30/60A |
Frequency Characteristics | 50/60 Hz |
Accuracy (50/60Hz) | 1.0 + 5 (0~30mA) 1.0 + 5 (0~50A) 5.0 + 5 (50~60A) |
Measurement Cycle | 2 times/second (Digital display), 12 times/second (Bar-graph display) |
Temperature Coefficient | 0.05% of range /°C or less (within the ranges of 0-18° and 28-50° for measurement of 0-50 A) |
Note |
|
Selection Guide
DC Current Range | - |
---|---|
DC Current Resolution | - |
AC Current Range | 3/30mA 30/60A |
AC Current Resolution | 0.001mA |
AC Current Frequency characteristics | 50/60Hz |
AC Current Method of detection | Mean Value |
AC Voltage Measurement | - |
DC Voltage Measurement | - |
Continuity Check Measurement | - |
Frequency Measurement | - |
Temperature Measurement | - |
Recorder output Function | - |
Waveform monitor output Function | - |
Data hold Function | O |
Auto hold Function | - |
Peak Hold Function | - |
Maximum value memory Function | - |
Mean value display Function | - |
Filter Function | - |
Range Hold Function | - |
Auto ZERO Adjust Function | - |
Auto power-off Function | O |
Additional Specification
At 23°C±5°C?75%RH or less
Accuracy: ±( % rdg + dgt) = ±(% readout + value of least significant digit)
AC current | 3/30mA, 30/60A | |
---|---|---|
Frequency characteristics | 50/60Hz | |
Accuracy | 50/60Hz | 1.0 + 5(0~30mA) |
1.0 + 5(0~50A) | ||
5.0 + 5 (50-60A) |
Overview:
0 Reviews Hide Reviews Show Reviews
Yokogawa
Yokogawa CL340 Clamp-on Tester, Leakage Current, 400 A
Yokogawa
Yokogawa CL320 Clamp-on Tester, Leakage Current, 200 A
Yokogawa
Yokogawa CL345 True-RMS Clamp-on Tester, Leakage Current, 400 A
Yokogawa
Yokogawa 322610 Leakage Current Tester (AC/DC) _
Yokogawa
Yokogawa CL360 AC Clamp-on Meter, Leakage Current, 100A
Yokogawa
Yokogawa CL155 Clamp-on AC Current Tester
Yokogawa
Yokogawa 96060 AC Clamp-on Probe for Leakage Current, 40mm, 2 A
Yokogawa
Yokogawa 30032A Leakage Clamp-on Tester with Sharp Low Pass Filter Function
Yokogawa