OPTO 22 - SNAP-ODC5-I _ SNAP 4-Ch Isolated 5-60 VDC Digital (Discrete) Output Module
- Brand
- OPTO 22
- SKU:
- SNAP-ODC5-I
OPTO 22 - SNAP-ODC5-I _ SNAP 4-Ch Isolated 5-60 VDC Digital (Discrete) Output Module
OPTO 22 - SNAP-ODC5-I _ SNAP 4-Ch Isolated 5-60 VDC Digital (Discrete) Output ModuleQuick Specs:
- SNAP 4-Ch Isolated 5-60 VDC Digital (Discrete) Output Module
Part of the SNAP PAC System, the module mounts on a SNAP PAC rack with a SNAP PAC brain or rack-mounted controller. Analog, digital, and serial I/O modules can all be on the same rack. Such an I/O unit is also well suited for PC-based control or for use as intelligent remote I/O for an Allen-Bradley Logix PLC system, such as ControlLogix, MicroLogix, or CompactLogix.
If you need Factory Mutual approved modules, see SNAP-ODC5-IFM.
For easier, faster wiring, see SNAP TEX cables and breakout boards.
Build your system in the SNAP I/O Configurator.
Specifications:
| SNAP-ODC5MA | SNAP-ODC5-i | SNAP-ODC5A-i | SNAP-ODC5ASNK |
Key Feature | Diagnostic switches | Four isolated channels | Four isolated channels | Load sinking |
Torque, hold-down screws | 4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) |
Torque, connector screws | 5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) |
Field Side Ratings (each channel) | ||||
Line Voltage - Range | 5 - 60 VDC | 5 - 60 VDC | 5 - 200 VDC | 5 - 200 VDC |
Line Voltage - Nominal | 5 - 48 VDC | 5 - 48 VDC | 5 - 200 VDC | 5 - 200 VDC |
Current Rating | 2 amps per module | 3 amps per module | 3 amps per module | 3 amps per module |
Surge Current | 1.5 amps peak for | 5 amps peak for | 5 amps peak for | 5 amps peak for |
Minimum Load | 20 mA | 20 mA | 20 mA | 20 mA |
Output Voltage Drop | 1.6 volts max.@ 0.75 amps | 1.6 volts max.@ 0.75 amps | 1.6 volts max.@ 0.75 amps | 1.6 volts max.@ 0.75 amps |
Off-state Leakage | 1 mA @ 60 VDC | 1 mA @ 60 VDC | 1 mA @ 200 VDC | 1 mA @ 200 VDC |
Peak Blocking Voltage | 60 VDC | 60 VDC | 200 VDC | 200 VDC |
Fuse | Has four isolated | Has four isolated | Has four isolated | 250 VAC - 4A 5x20 mm |
Channel-to-channel | 300 VAC | 300 VAC | 300 VAC | Not applicable |
Logic Side Ratings | ||||
Pickup Voltage | 4 V @ 5.5 mA | 4 V @ 5.5 mA | 4 V @ 5.5 mA | 4 V @ 5.5 mA |
Dropout Voltage | 1 VDC | 1 VDC | 1 VDC | 1 VDC |
Control Resistance | 220 ohms | 220 ohms | 220 ohms | 220 ohms |
Logic Supply Voltage | 5 VDC ± 0.25 VDC | 5 VDC ± 0.25 VDC | 5 VDC ± 0.25 VDC | 5 VDC ± 0.25 VDC |
Logic Supply Current | 50 mA maximum | 50 mA maximum | 50 mA maximum | 50 mA maximum |
Module Ratings | ||||
Number of Channels Per Module | 4 | 4 | 4 | 4 |
Turn-on Time | 100 usec | 100 usec | 100 usec | 100 usec |
Turn-off Time | 750 usec | 750 usec | 750 usec | 750 usec |
Isolation (Field Side to Logic Side) | 4,000 volts (transient) | 4,000 volts (transient) | 4,000 volts (transient) | 4,000 volts (transient) |
Temperature | -20 ° to 70 °C, operating | -20 ° to 70 °C, operating | -20 ° to 70 °C, operating | -20 ° to 70 °C, operating |
Wire size range | 22 to 14 AWG | 22 to 14 AWG | 22 to 14 AWG | 22 to 14 AWG |
Agency Approvals | UL, CE, RoHS, DFARS; UKCA | UL, CE, RoHS, DFARS; UKCA | UL, CE, RoHS, DFARS; UKCA | UL, CE, RoHS, DFARS; UKCA |
Warranty | 30 months | Lifetime | Lifetime | Lifetime |