OPTO 22 - SNAP-ODC-32-SRC _ SNAP 32-channel Digital (Discrete) Output Module, 5-60 VDC Load Sourcing
- Brand
- OPTO 22
- SKU:
- SNAP-ODC-32-SRC
OPTO 22 - SNAP-ODC-32-SRC _ SNAP 32-channel Digital (Discrete) Output Module, 5-60 VDC Load Sourcing
OPTO 22 - SNAP-ODC-32-SRC _ SNAP 32-channel Digital (Discrete) Output Module, 5-60 VDC Load SourcingQuick Specs:
- SNAP 32-channel Digital (Discrete) Output Module
- 5-60 VDC Load Sourcing
If you're unsure whether you need a sinking or sourcing module, see the sinking/sourcing demo or watch the brief Sinking vs. Sourcing video.
Part of the SNAP PAC System, the module mounts on a SNAP PAC rack with a SNAP PAC brain or rack-mounted controller. Analog, digital, and serial I/O modules can all be on the same rack. Such an I/O unit is also well suited for PC-based control or for use as intelligent remote I/O for an Allen-Bradley Logix PLC system, such as ControlLogix, MicroLogix, or CompactLogix.
For easy field wiring, use the SNAP-ODC-HDB or compact SNAP-UDC-HDB breakout rack and the SNAP-HD-BF6 header cable. A wiring harness with flying leads (SNAP-HD-CBF6) is also available.
To switch larger loads, use the module with two SNAP-TEX-MR10-16C breakout boards, which have mechanical relays that allow you to switch loads up to 10 amps. Easily connect the module to the boards using the SNAP-HD-G4F6 cable, which simply plugs into both the module and the boards.
NOTE: If you need a Factory Mutual-approved version, see the SNAP-ODC-32-SRC-FM module instead.
For switching signals with higher current, see the SNAP-UDC-HDB-G4 breakout board, which mounts G4 input modules that handle up to 3 amps per point (G4 modules are sold separately).
Reference Charts: Build your system in the SNAP I/O Configurator.
Specifications:
| SNAP-ODC-32-SRC | SNAP-ODC-32-SNK |
Switching Voltage | 5 - 60 VDC | 5 - 60 VDC |
Nominal Switching Voltage | 12 - 24 VDC | 12 - 24 VDC |
Logic Voltage and Current | 5 VDC ± 0.1 @ 150 mA | 5 VDC ± 0.1 @ 150 mA |
Maximum Off State Voltage | 60 VDC | 60 VDC |
Output Leakage, Typical | <10 microamps per channel (60 V, 70 °C) | <10 microamps per channel (60 V, 70 °C) |
Maximum Load per Point | 0.25 A | 0.25 A |
Voltage Drop | 0.15 VDC @ 0.25 A | 0.15 VDC @ 0.25 A |
Surge (1 sec.) | 1 A | 1 A |
Output Arrangement | 32 output channels; 4 groups of 8 outputs each. Points in each group share a common positive connection. | 32 output channels; 4 groups of 8 outputs each. Points in each group share a common negative connection. |
Maximum Operating | 250 V | 250 V |
Isolation: Field to Logic | 1500 V | 1500 V |
Output Turn-On/Off Time | 100 microseconds | 100 microseconds |
Polling time from I/O processor to module1 | 2 - 30 ms typical2 | 2 - 30 ms typical2 |
Indicators | None; use optional OptoTerminal-G20 diagnostic display or breakout rack. | None; use optional OptoTerminal-G20 diagnostic display or breakout rack. |
Maximum Number of HDD Modules on One Mounting Rack | 16 | 16 |
Torque, hold-down screws | 4 in-lb (0.45 N-m) | 4 in-lb (0.45 N-m) |
Torque, connector screws | 5.26 in-lb (0.6 N-m) | 5.26 in-lb (0.6 N-m) |
Operating Temperature | -20 to 70 °C | -20 to 70 °C |
Storage Temperature | -40 to 85 °C | -40 to 85 °C |
Agency Approvals | SNAP-ODC-32-SRC: UL, CE, RoHS, DFARS; UKCA SNAP-ODC-32-SRC-FM: CE, FM, RoHS, DFARS; UKCA | SNAP-ODC-32-SNK: UL, CE, RoHS, DFARS; UKCA SNAP-ODC-32-SNK-FM: CE, FM, RoHS, DFARS; UKCA |
Warranty | Lifetime | Lifetime |
1 Affects turn-on and turn-off determination |