OPTO 22 - SNAP-AIRTD-8U _ SNAP 8-Ch Multifunction RTD/Resistance Analog Temperature Input Module
- Brand
- OPTO 22
- SKU:
- SNAP-AIRTD-8U
OPTO 22 - SNAP-AIRTD-8U _ SNAP 8-Ch Multifunction RTD/Resistance Analog Temperature Input Module
OPTO 22 - SNAP-AIRTD-8U _ SNAP 8-Ch Multifunction RTD/Resistance Analog Temperature Input ModuleQuick Specs:
- SNAP 8-Ch Multifunction RTD/Resistance Analog Temperature Input Module
The SNAP-AIRTD-8U analog input module provides 8 input channels, each individually software configurable. This module is commonly used for 3-wire RTD temperature inputs but is also suited to high-resolution resistance measurements. It features open circuit detection if any wire breaks.
You can individually configure each of the module's 8 points for a variety of behaviors, including a fixed temperature range for nickel, platinum, or copper RTD inputs; a fixed range in ohms; or two types of auto-ranging where the module scrolls within a range (in ohms) and chooses the best resolution.
The SNAP-AIRTD-8U has a plug-in terminal on top with spring-clamp connectors for easy wiring. An insertion tool is provided in the box with the module.
All 8 inputs share the same reference terminal. Make sure you use isolated RTD probes.
The SNAP-AIRTD-8U requires a SNAP PAC brain or R-series controller with firmware R9.5a or higher. The module cannot be used with legacy brains or controllers.
Specifications:
| SNAP-AIRTD-8U | ||
3-wire RTD input and maximum temperature table range (actual range depends on your probe) | 1000 ohm platinum @ 0 °C ñ= 0.00385 | 100 ohm platinum @ 0 °C | 10 ohm copper @ 25 °C |
1000 ohm nickel @ 0 °C | 100 ohm nickel @ 0 °C | ||
1000 ohm nickel @ 70 °F | 120 ohm nickel @ 0 °C | ||
Input Range | 0 to 4000 ohms | 0 to 400 ohms | 0 to 40 ohms |
Accuracy | 0.8 °C (Pt); 0.6 °C (Ni) | 0.8 °C (Pt); 0.6 °C (Ni) | 1.7 °C |
Excitation Current | 0.325 mA | 2 mA | 4.28 mA |
Over-Range Limit | 10% overrange for all measurements in ohms | ||
Resolution | The greater of: (Ohms Range / 100,000) or 1 milliohm Better than or equal to 0.05 °C (0.09 °F) | ||
Input Filtering | -15 dB @ 50 Hz, -20 dB @ 60 Hz 20 Hz (-3 DdB = 5.24 Hz) | ||
Data Freshness (Max) | 1.2 s | ||
Auto-range Settle Time Step change from 10 to 8000 Step change from 8000 to 10 | 1.2 s to the next higher or lower range <= 10 s ranging up (channel may show overrange until settled) <= 10 s ranging down (channel will give a reading while settling) | ||
Total Lead Resistance | 200 ohms maximum | ||
DC Common Mode Rejection | >-120 dB | ||
AC Common Mode Rejection | >-120 dB at 60 Hz | ||
Maximum Survivable Fault Voltage at Input (between any 2 field wires) | ±8 V | ||
Maximum Operating Common Mode Voltage | 250 V field terminal to logic connector | ||
Isolation | 1500 V field side to logic side | ||
Power Requirements | 5.00 to 5.20 VDC @ 135 mA | ||
Operating Temperature | -20 °C to 70 °C | ||
Storage Temperature | -40 °C to 85 °C | ||
Humidity | 5-95%, non-condensing | ||
Maximum wire size | 20 AWG | ||
Torque, hold-down screws | 4 in-lb (0.45 N-m) | ||
Agency Approvals | UL, CE, RoHS, DFARS; UKCA | ||
Warranty | Lifetime |