OPTO 22 - ODC5P _ Flat Pak output module, 5-60 VDC
OPTO 22 - ODC5P _ Flat Pak output module, 5-60 VDCQuick Specs:
- Flat Pak output module
- 5-60 VDC
Because of their low profile, Flat Pak modules are ideal for user-designed printed circuit boards where the standard single-channel or Quad Pak modules do not provide an exact fit.
The ODC5P handles 5-60 VDC. This module is used for controlling or switching DC loads. The module provides up to 4000 V of optical isolation between field inputs and the logic side of the circuit.
Typical uses and applications include switching the following loads:
- DC relays
- DC solenoids
- DC motor starters
- DC lamps or indicators
Specifications:
| OAC5P | ODC5P |
Operating Voltage Range | 12 - 140 VAC | 5 - 60 VDC |
Line Voltage, Nominal | 120 VAC | n/a |
Current Rating | 3 A @ 45 °C ambient 2 A @ 70 °C ambient | 3 A @ 45 °C ambient 2 A @ 70 °C ambient |
Off-state Leakage at Maximum Voltage | 5 mA, rms | 1 mA |
Logic Voltage, Nominal | 5 VDC | 5 VDC |
Logic Voltage Range (Vcc) | 2.5 - 8 VDC | 2.5 - 8 VDC |
Logic Pickup Voltage | 2.55 VDC | 2.5 VDC |
Logic Dropout Voltage | 1 VDC | 1 VDC |
Logic Input Current at Normal Logic Voltage | 12 mA | 12 mA |
Control Resistance (Rc in Schematic Diagram) | 220 Ohms | 220 Ohms |
One-second Surge | n/a | 5 A |
One-cycle Surge | 80 A peak | n/a |
Peak Repetitive Voltage | 500 V | n/a |
Minimum Load Current | 20 mA | n/a |
Operating Frequency | 25 - 65 Hz | n/a |
Turn-on Time | 1/2 cycle maximum, zero voltage | 100 microseconds |
Turn-off Time | 1/2 cycle maximum, zero current | 750 microseconds |
DV/DT, Off-state | 200 V/microsecond | n/a |
DV/DT, Commutating | Snubbed for rated 0.5 power factor load | n/a |
Output Voltage Drop Maximum Peak | 1.6 V | 1.6 V |
Operating Temperature | - 30 to 70 °C | - 30 to 70 °C |
Agency Approvals | UL (E58169), CSA (35852) | UL (E58169), CSA (35852) |
Warranty | Lifetime | Lifetime |