OPTO 22 - ODC24A _ DC Output 5-200 VDC, 24 VDC Logic
OPTO 22 - ODC24A _ DC Output 5-200 VDC, 24 VDC LogicQuick Specs:
- DC Output 5-200 VDC
- 24 VDC Logic
Typical uses and applications for DC output modules include switching the following loads:
- DC relays
- DC solenoids
- DC motor starters
- DC lamps or indicators
- PLC logic
ODC24A modules are not for use with Opto 22 modules.
Specifications:
| One-second Surge | 5 A |
| Operating Ambient Temperature | -30 °C to 70 °C |
| Isolation, Input-to-Output (Transient) | 4000 volts |
| Turn-on Time | 100 µs |
| Turn-off Time | 750 µs |
| Output Voltage Drop Maximum Peak | 1.6 volts |
Module Specifications
|
| UNITS | ODC5 | ODC5A | ODC15* | ODC15A* | ODC24* | ODC24A* |
| Line voltage - max. | VDC | 60 | 200 | 60 | 200 | 60 | 200 |
| Operating voltage range | VDC | 5 - 60 | 5 - 200 | 5 - 60 | 5 - 200 | 5 - 60 | 5 - 200 |
| Current rating | Amps | 3 | 1 | 3 | 1 | 3 | 1 |
| UL Motor Load rating | Amps | 1.5 | 1 | 1.5 | 1 | 1.5 | 1 |
| Off-state leakage @ max. voltage | mA | 1 | 2 | 1 | 2 | 1 | 2 |
| Logic voltage - nominal | VDC | 5 | 5 | 15 | 15 | 24 | 24 |
| Logic voltage range (Vcc) | VDC | 2.5 - 8 | 2.5 - 8 | 9 - 16 | 9 - 16 | 18 - 32 | 18 - 32 |
| Logic pickup voltage | VDC | 2.5 | 2.5 | 9 | 9 | 18 | 18 |
| Logic dropout voltage | VDC | 1 | 1 | 1 | 1 | 1 | 1 |
| Logic input current | mA | 12 | 12 | 15 | 15 | 18 | 18 |
| Control resistance | Ohms | 220 | 220 | 1K | 1K | 2.2K | 2.2K |
| * Not for use with Opto 22 brains. | |||||||