OPTO 22 - IAC5A _ G1 AC Digital Input, 180-280 VAC, 5 VDC Logic
OPTO 22 - IAC5A _ G1 AC Digital Input, 180-280 VAC, 5 VDC LogicQuick Specs:
- G1 AC Digital Input
- 180-280 VAC
- 5 VDC Logic
The IAC5 input module is used to sense ON/OFF AC voltage levels at 180-280 VAC. All AC input modules are designed with filtering on the input and a hysteresis amplifier for high noise rejection and transient-free clean switching. Each module provides up to 4000 volts (transient) of optical isolation between the field inputs and the logic output of the circuit.
Typical uses and applications include sensing the presence or absence of voltage or sensing contact closures from sources such as:
- Proximity switches
- Limit switches
- Float switches
- Selector switches
- Push buttons
- Toggle switches
- Thermostats
Specifications:
General
Operating Ambient Temperature | - 30 to 70 °C |
Isolation, Input-to-Output (Transient) | 4000 V |
Output Voltage Drop: logic side | 0.4 volts @ 50 mA |
Output Current | 50 mA |
Output Leakage With No Input | 0.1 mA @ 30 VDC |
Transistor | 30 volts breakdown |
Input Module Specifications
| Unit | IDC5 | IDC5B | IDC5D | IDC5G | IDC15 | IDC24 |
Input Voltage Range | VDC | 10 - 32 | 4 - 16 | 2.5 - 28 | 35 - 60 | 10 - 32 | 10 - 32 |
VAC | 12 - 32 | 4 - 16 | 35 - 60 | 12 - 32 | 12 - 32 | ||
Input Current @ Max Line | mA | 25 | 45 | 30 | 6 | 25 | 25 |
Turn-on Time | msec | 5 | 0.05 | 1 | 10 | 5 | 5 |
Turn-off Time | msec | 5 | 0.1 | 1.5 | 10 | 5 | 5 |
Input Allowed for No Output | mA | 1 | 0.7 | 0.2 | 0.7 | 1 | 1 |
Volts | 3 | 1 | 1 | 7 | 3 | 3 | |
Output Supply | VDC | 5 | 5 | 5 | 5 | 15 | 24 |
Output Supply | VDC | 4.5 - 6 | 4.5 - 6 | 4.5 - 6 | 4.5 - 6 | 12 - 18 | 20 - 30 |
Output Supply Current | mA | 12 | 12 | 12 | 12 | 15 | 18 |
Input Resistance | Ohms | 1.5k | 300 | 900 | 10k | 1.5k | 1.5k |
Control Resistance | Ohms | 220 | 220 | 470 | 220 | 1k | 2.2k |
| Unit | IAC5 | IAC15 | IAC24 | IAC5A | IAC15A | IAC24A |
Input Voltage Range | VDC | 90 - 140 | 90 - 140 | 90 - 140 | 180 - 280 | 180 - 280 | 180 - 280 |
VAC | 90 - 140 | 90 - 140 | 90 - 140 | 180 - 280 | 180 - 280 | 180 - 280 | |
Input Current @ Max Line | mA | 5 | 5 | 5 | 5 | 5 | 5 |
Turn-on Time | msec | 20 | 20 | 20 | 20 | 20 | 20 |
Turn-off Time | msec | 20 | 20 | 20 | 20 | 20 | 20 |
Input Allowed for No Output | mA | 3 | 3 | 3 | 1 | 1 | 1 |
Volts | 45 | 45 | 45 | 45 | 45 | 45 | |
Output Supply | VDC | 5 | 15 | 24 | 5 | 15 | 24 |
Output Supply | VDC | 4.5 - 6 | 12 - 18 | 20 - 30 | 4.5 - 6 | 12 - 18 | 20 - 30 |
Output Supply Current | mA | 12 | 15 | 18 | 12 | 15 | 15 |
Input Resistance | Ohms | 28k | 28k | 28k | 70k | 70k | 70k |
Control Resistance | Ohms | 220 | 1k | 2.2k | 220 | 1k | 2.2k |