OPTO 22 - GRV-ITR-12 _ Thermistor, 12 ch, non-isolation
Write a Review
OPTO 22
OPTO 22 - GRV-ITR-12 _ Thermistor, 12 ch, non-isolation
- Brand
- OPTO 22
- SKU:
- GRV-ITR-12
- UPC:
OPTO 22 - GRV-ITR-12 _ Thermistor, 12 ch, non-isolation
Quick Specs:
- Thermistor
- 12 ch
- non-isolation
OPTO 22 - GRV-ITR-12 _ Thermistor, 12 ch, non-isolation
Quick Specs:
- Thermistor
- 12 ch
- non-isolation
The GRV-ITR-12 module is part of the groov EPIC® system. This module has 12 channels of analog to digital conversion that convert resistance to temperature or to Ohms.
The module is ideal for NTC thermistors commonly used in HVAC, refrigeration, and process control applications. It may also be used with PTC thermistors in resistance sensing applications. The module has 12 channels of analog to digital conversion that convert resistance to temperature or to Ohms. The module reads variable resistance type transducers, with input ranges from 500 Ohms to 400 K Ohms, plus Autorange. You can also select from predefined curves for popular thermistors, as well as create custom curves. The module also offers options to decrease data refresh time and step input response time.
The GRV-ITR-12 module mounts on a groov EPIC® chassis with a GRV-EPIC-PR1 processor and assorted discrete, analog, and serial groov I/O modules.
Specifications:
Features | GRV-IRTD-8 | GRV-ITR-12 |
---|---|---|
Scaling | x | x |
Offset and Gain | x | x |
Minimum/Maximum Values | x | x |
Average Filter Weight | x | x |
Simple Moving Average (SMA) | x | x |
Analog Totalizing | x | x |
Problem indication | x | x |
Specification | GRV-ITR-12 |
---|---|
Input Ranges (Ohms) | 400 k, 200 k, 100 k, 50 k, 40 k, 20 k, 10 k, 5 k, 4 k, 2 k, 1 k, 500 and Autorange |
Accuracy, normal mode (Ohms @ Range) | 0.1%; specific values for indicated range: 400@400 k, 200@200 k, 100@100 k, 50@50 k, 40@40 k, 20@20 k, 10@10 k, 5@5 k, 4@4 k, 2@2 k, 1@1 k, 0.5@500 |
Accuracy, fast ADC mode (Ohms @ Range) | 0.5%; specific values for indicated range: 2000@400 k, 1000@200 k, 500@100 k, 250@50 k, 200@40 k, 100@20 k, 50@10 k, 25@5 k, 20@4 k, 10@2 k, 5@1 k, 2.5@500 |
Excitation Current (Range & Load Watts Dissipated) | >7.9 µA (400 K & 25 µW), (200 K & 12.4 µW), (100 K & 6.2 µW), (50 K & 3.1 µW), >84.7 µA (40 K & 287 µW), (20 K & 144 µW), (10 K & 72 µW), (5 K & 36 µW), >169.2 µA (4 K & 115 µW), (2 K & 57 µW), (1 K & 29 µW), (500 & 14 µW) |
Analog Data Filtering | -3 dB @ 2.4 Hz -25 dB @ 60 Hz |
Software Filtering: Simple Moving Average | 1 to 32 readings |
Software Filtering: Weighted Average | 1 to 4096 |
Data Refresh Time (normal mode) | 900 ms |
Data Refresh Time (fast ADC mode) | 450 ms |
Step Input Response Time (normal mode) | 900 ms x SMA value (for example, 28.8 s @ 32 SMA, Default SMA = 4) |
Step Input Response Time (fast ADC mode) | 450 ms x SMA value (for example, 14.4 s @ 32 SMA, Default SMA = 4) |
Problem Indication | out of range |
Isolation (field-to-logic) | 300 V working, 1500 V transient (1 minute) |
Isolation (channel-to-channel) | 300 V between channel group 0 - 5 & channel group 6 - 11. None within a group. |
Number of Channels | 12 |
Chassis Power Consumption | 1.3 W |
Minimum groov EPIC Firmware Version | 1.3.0 |
Minimum PAC Project Version | 10.2000 |
Minimum Library Package for CODESYS Version | 1.0.0.0 |
Wire Size | 28 - 14 AWG |
Torque, connector screw | 2.5 in-lb (0.28 N-m) |
Torque, hold-down screw | 3.5 in-lb (0.4 N-m) |
Temperature (operating) | -20 °C to +70 °C |
Temperature (storage) | -40 °C to +85 °C |
Humidity (non-condensing) | 5 - 95% RH |
Agency Approvals | UL/cUL(Class 1 Div. 2), CE, ATEX(Category 3, Zone 2), RoHS, DFARS; UKCA |
Warranty | Lifetime |
0 Reviews Hide Reviews Show Reviews
OPTO 22
OPTO 22 - GRV-IICTD-12 _ GRV 12 CHANNEL ICTD INPUT MODULE
OPTO 22
OPTO 22 - GRV-OACI-12 _ AC digital output, 12 channels, 12-250 VAC, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-IACIHV-12 _ AC input, 12 channels, 180-280 VAC, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-IDCI-12 _ DC digital input, 12 channels, 10-30 V, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-ODCI-12 _ DC digital output, 12 channels, 5-60 VDC, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-IACI-12 _ AC digital input, 12 channels, 85-140 VAC, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-OACIS-12 _ AC digital output, 12 channels, 12-250 VAC, channel-to-channel isolation, on/off only
OPTO 22
OPTO 22 - GRV-IVI-12 _ Analog input, multiple ranges, ±1.25 to ±160 V, isolated, 12 channels
OPTO 22