Quick Specs:
- 12 Channel Self-Wetting Input Module
OPTO 22 - GRV-IDCSW-12 _ 12 Channel Self-Wetting Input Module
Quick Specs:
- 12 Channel Self-Wetting Input Module
Part of the groov EPIC® system, the GRV-IDCSW-12 mounts on a groov EPIC® chassis alongside other discrete, analog, and serial groov I/O modules and a GRV-EPIC-PR1 processor.
Specifications:
| Feature | GRV-IDC-24 | GRV-IDCS-24 | GRV-IDCSW-12 | GRV-IDCI-12 | GRV-IDCIS-12 | GRV-IDCIFQ-12 |
|---|---|---|---|---|---|---|
| Number of channels | 24 | 24 | 12 | 12 | 12 | 12 |
| Channel-to-channel isolation |
|
|
| x | x | x |
| On/off state | x | x | x | x | x | x |
| On/off latching | x |
| x | x |
| x |
| Counting | x |
| x | x |
| x |
| On/off totalization | x |
| x | x |
| x |
| Frequency measurement | x |
| x | x |
| x |
| Period measurement | x |
| x | x |
| x |
| Pulse measurement | x |
| x | x |
| x |
| Quadrature |
|
|
|
|
| x |
| Specification | GRV-IDCSW-12 |
|---|---|
| Open Circuit Voltage (Switch Open) | > 20 V |
| Channel Current Limit | 2.0 mA ±25% |
| Channel Operating Current | 0.7 mA typical |
| Minimum Off Resistance | 50 KOhms |
| Maximum On Resistance | 10 KOhms |
| Turn ON Characteristic | > 5 V |
| Turn OFF Characteristic | < 1.5 V |
| Maximum Continuous Survivable Input Voltage | 32 V |
| Input Impedance | 3.9 KOhms |
| Max. Freq. (50% square wave) | 80 Hz |
| Debounce Time | > 500 microseconds |
| Isolation (field-to-logic) | 300 V working, 1500 V transient (1 minute) |
| Isolation (channel-to-channel) | None |
| Number of Channels | 12 |
| Chassis Power Consumption | 2.4 W |
| Minimum GRV-EPIC-PR1 Firmware Version | 1.4.2 |
| Minimum PAC Project Version | 10.2003 |
| Minimum Library Package for CODESYS Version | 1.0.2.0 |
| Wire Size | 28-14 AWG |
| Torque, connector screw | 2.5 in-lb (0.28 N-m) |
| Torque, hold-down screw | 3.5 in-lb (0.4 N-m) |
| Temperature (operating) | -20 °C to +70 °C |
| Temperature (storage) | -40 °C to +85 °C |
| Relative Humidity (non-condensing) | 5-95% |
| Agency Approvals | UL/cUL(Class 1 Div. 2); CE, ATEX(Category 3, Zone 2), RoHS; DFARS; CB Scheme; UKCA |
| Warranty | Lifetime |
0 Reviews Hide Reviews Show Reviews
OPTO 22
OPTO 22 - GRV-IICTD-12 _ GRV 12 CHANNEL ICTD INPUT MODULE
OPTO 22
OPTO 22 - GRV-ITM-12 _ Analog input, 12 channels, thermocouple or mV
OPTO 22
OPTO 22 - GRV-IACIHV-12 _ AC input, 12 channels, 180-280 VAC, channel-to-channel isolation
OPTO 22
OPTO 22 - GRV-IDCI-12 _ DC digital input, 12 channels, 10-30 V, channel-to-channel isolation
OPTO 22