OPTO 22 - GRV-IACHVS-24 _ AC input, 24 channels, 180-280 VAC, on/off state only
$300.00
- Brand
- OPTO 22
- SKU:
- GRV-IACHVS-24
OPTO 22 - GRV-IACHVS-24 _ AC input, 24 channels, 180-280 VAC, on/off state only
Quick Specs:
- AC input
- 24 channels
- 180-280 VAC
- on/off state only
The GRV-IACHVS-24 digital input module can sense status from up to 24 devices such as pumps, fans, and motors that use a 180 - 280 VAC signal. This module provides only on or off sensing, offering a lower cost option for projects with simple requirements.
The GRV-IACHVS-24 module mounts on a groov EPIC® chassis alongside other digital, analog, and serial I/O modules, to provide the mix of signals you need at any location.
NOTE: If your application requires a larger set of features (latching, totalization, and so on) in addition to on/off status, see the GRV-IACHV-24.
If you require channel-to-channel isolation, see the GRV-IACIHV-12.
The GRV-IACHVS-24 module mounts on a groov EPIC® chassis alongside other digital, analog, and serial I/O modules, to provide the mix of signals you need at any location.
NOTE: If your application requires a larger set of features (latching, totalization, and so on) in addition to on/off status, see the GRV-IACHV-24.
If you require channel-to-channel isolation, see the GRV-IACIHV-12.
Specifications:
Feature | GRV-IACHV-24 | GRV-IACHVS-24 | GRV-IACIHV-12 | GRV-IACIHVS-12 |
Number of channels | 24 | 24 | 12 | 12 |
Channel-to-channel isolation | x | x | ||
On/off state | x | x | x | x |
On/off latching | x | x | ||
On/off totalization | x | x | ||
Frequency measurement | x | x | ||
Period measurement | x | x | ||
Pulse measurement | x | x |
Specification | GRV-IACHV-24 | GRV-IACHVS-24 | GRV-IACIHV-12 | GRV-IACIHVS-12 |
Nominal Input Voltage Range (RMS) | 180 - 280 VAC | 180 - 280 VAC | 180 - 280 VAC | 180 - 280 VAC |
Turn-on Voltage | 180 VAC | 180 VAC | 180 VAC | 180 VAC |
Turn-off Voltage | 35 VAC | 35 VAC | 35 VAC | 35 VAC |
Input Impedance (±5%) | 532 kOhms | 532 kOhms | 271 kOhms | 271 kOhms |
Operating Frequency | 40 Hz to 400 Hz | 40 Hz to 400 Hz | 40 Hz to 400 Hz | 40 Hz to 400 Hz |
Turn-on Time (typical) | 30 ms at V | 30 ms at V | 30 ms at V | 30 ms at V |
Turn-off Time (typical) | 30 ms at V | 30 ms at V | 30 ms at V | 30 ms at V |
Isolation (field-to-logic) | 300 VAC, 1500 V Transient | 300 VAC, 1500 V Transient | 300 VAC, 1500 V Transient | 300 VAC, 1500 V Transient |
Isolation (channel-to-channel) | N/A | N/A | 300 VAC working | 300 VAC working |
Number of Channels | 24 | 24 | 12 | 12 |
Chassis Power Consumption | 1.0 W | 1.0 W | 1.0 W | 1.0 W |
Wire Size | 28 - 14 AWG | 28 - 14 AWG | 28 - 14 AWG | 28 - 14 AWG |
Torque, connector screw | 2.5 in-lb (0.28 N-m) | 2.5 in-lb (0.28 N-m) | 2.5 in-lb (0.28 N-m) | 2.5 in-lb (0.28 N-m) |
Torque, hold-down screw | 3.5 in-lb (0.4 N-m) | 3.5 in-lb (0.4 N-m) | 3.5 in-lb (0.4 N-m) | 3.5 in-lb (0.4 N-m) |
Temperature (operating) | -20 °C to +70 °C | -20 °C to +70 °C | -20 °C to +70 °C | -20 °C to +70 °C |
Temperature (storage) | -40 °C to +85 °C | -40 °C to +85 °C | -40 °C to +85 °C | -40 °C to +85 °C |
Relative Humidity (non-condensing) | 5 - 95% | 5 - 95% | 5 - 95% | 5 - 95% |
Agency Approvals | UL/cUL (Class 1 Div. 2)a; CE, ATEX (Category 3, Zone 2), RoHS; DFARS; CB Scheme; UKCA | |||
Warranty | Lifetime | Lifetime | Lifetime | Lifetime |
a For use in hazardous locations, equipment must be mounted in an enclosure that meets the requirements of the National Electrical Code, ANSI/NFPA 70, and ANSI/ISA-61010-1 (82.02.01). |