Absolute Process Instruments
Absolute Process Instruments APD 4930 D _ Specify VDC or mADC range
- Brand
- Absolute Process Instruments
- SKU:
- APD 4930 D
- UPC:
Absolute Process Instruments APD 4930 D _ Specify VDC or mADC range
Cecomp Electronics, APD 4930 D, IsoSplitter® Signal Split
Absolute Process Instruments APD 4930 D _ Specify VDC or mADC range
Cecomp Electronics, APD 4930 D, IsoSplitter® Signal Splitter 1 DC Input to 2 DC Output, 9-30 VAC/VDC Power
Features with all optional accessories:
- One Input to Two Outputs with Full Isolation
- Zero and Span Output Calibration Potentiometers
- Full 1200 V Input / Output / Power Isolation
- Output LoopTracker® LEDs
- Output Test/Manual Override for Each Channel
- Built-In Loop Power Supply for Sink/Source Input
Applications:
- Split, Convert, Boost, and Rescale Process Signals
- Split Process Signals for Control and Validation
- Interface a Process Signal with Multiple Panel Meters, PLCs, Recorders, Data Acq., DCS, & SCADA Systemsy
The APD 4930 D IsoSplitter accepts a DC voltage or current input and provides two optically isolated DC voltage or current outputs that are linearly related to the input. The input range and each output range are independent and can be specified as required. This provides an economical solution when one signal must be sent to two different devices.
Typical applications include isolation, output splitting, output device separation and redundancy (i.e. to prevent failure of the entire loop if one device fails), or a combination of these.
The input signal is filtered, amplified, split, and then passed through an opto-coupler to the output stages. Full 4-way isolation (input, output 1, output 2, power) make this module useful for ground loop elimination, common mode signal rejection, and noise pickup reduction.
Independent Output
Each output channel is factory ranged to your specifications and provides an optically isolated DC voltage or current output that is linearly related to the input. Sourcing mA outputs are standard. Sinking milliamp or high voltage outputs are optional.
Isolation
The full 4-way (input, output 1, output 2, power) isolation makes this module useful for ground loop elimination, common mode signal rejection or noise pickup reduction.
LoopTracker
API exclusive features include two LoopTracker LEDs (one for each output channel) that vary in intensity with changes in the process output signals. These provide a quick visual picture of your process loop at all times and can greatly aid in saving time during initial startup and/or troubleshooting.
Specifications Table:
Input | Factory configured: 0-100 mV to 0-300 V, ±100 mV to ±10 V, 0-1 mA to 0-1000 mA, 4-20 mA |
Output | Factory configured: 0-1 V to 0-10 V, optional up to 20 V, ±1 V to ±10 V, 0-1 mA to 20 mA, 4-20 mA |
DC Input Range | Factory configured, please specify input range or consult factory for special ranges.
|
Input Impedance |
|
Input Loop Power Supply | 15 VDC ±10%, regulated, 25 mADC. May be selectively wired for sinking or sourcing mA input |
Channel 1 and Channel 2 DC Output Ranges | Factory configured, please specify for each output channel Outputs are independent and do not need to be the same
|
Output Calibration | Multi-turn zero and span potentiometers for each output channel (±15% of span adjustment range typical) |
Output Loop Power Supply | 20 VDC nominal, regulated, 25 mADC for each output channel. May be selectively ordered for sinking mA output |
Output Test/Manual Override | Output test level factory set to 50 % of span. Specify if special output percentage levels are required |
Output Ripple and Noise | Less than 10 mVRMS ripple and noise |
Linearity | Better than ±0.1% of span |
Ambient Temperature Range and Stability |
|
Response Time | 70 milliseconds nominal |
Isolation | Full 4-way, 1200 VRMS minimum |
Installation Environment |
|
Connectors | Four 4-terminal removable connectors, 14 AWG max wire size |
Power | 9-30 VDC or 10-32 VAC 50/60 Hz, 6 W maximum |
0 Reviews Hide Reviews Show Reviews
Absolute Process Instruments
Absolute Process Instruments APD 4930 _ Specify VDC or mADC range
Absolute Process Instruments
Absolute Process Instruments APD 44L3 D _ Specify VDC or mADC range
Absolute Process Instruments
Absolute Process Instruments APD 44L2 D _ Specify VDC or mADC range
Absolute Process Instruments
Absolute Process Instruments APD 4406 D _ Specify VDC or mADC range
Absolute Process Instruments
Absolute Process Instruments APD 4408 D _ Specify VDC or mADC range
Absolute Process Instruments
Absolute Process Instruments APD 4402 D _ Specify VDC or mADC range
Absolute Process Instruments
Absolute Process Instruments APD 4403 D _ Specify VDC or mADC range
Absolute Process Instruments
Absolute Process Instruments APD 44H4 D _ Specify VDC or mADC range
Absolute Process Instruments