AEMC AC Current Probe Model SR634
$309.00
- Brand
- Aemc
- SKU:
- 2113.48
- UPC:
- 6.85E+11
- Availability:
- DISCONTINUED WITHOUT A REPLACEMENT, NO STOCK
AEMC SR634 Description:
This a general purpose 1000AAC current probe designed for use with instruments that require a 5A current input. It works as a traditional current transformer (with ratios of 250:5, 500:5 or 1000:5) and has an output of 5mA per amp measured in the jaw. The SR634 has jack output termination that accept 4mm banana plugs. The rounded jaw design on this probe makes it well-suited for power applications where high accuracy and low phase shift is important.
Features
- Measurement range of 100mA to 1200AAC
- Large jaw opening accommodates conductors up to two 500kcmil
- Improved ergonomic design and easy operation
- Conforms to EN 61010, 600V CAT III
- Low phase shift for power measurement
- Designed for DMMs, recorders, loggers, oscilloscopes, power and harmonic meters
Applications
- Power quality measuring
- Large industrial loads
- Measuring around cable bundles
- Power load monitoring
- Waveform analysis
AEMC SR634 Specifications:
Nominal Range | 250, 500, 1000A |
Measurement Range | 0.1 to 1200A |
Transformation Ratio | 250:5, 500:5, 1000:5 |
Output Signal | 5mA, 10mA, 20mA AC/A AC (5A AC at 250, 500 or 1000A) |
Accuracy (250A Range) | 1 to 5A: ?10% ± 0.1A 5A: 10% of Reading 12.5A: 5% of Reading 50A: 2.5% of Reading 250A: 2% of Reading 300A: 2% of Reading |
Phase Shift (250A Range) | 12.5A: 10° 50A: 10° 250A: 10° 300A: 10° |
Accuracy (500A Range) | 1 to 10A: ?6% ± 0.1A 10A: 6% of Reading 25A: 3% of Reading 100A: 2% of Reading 500A: 1% of Reading 600A: 1% of Reading |
Phase Shift (500A Range) | 10A: 6° 25A: 4° 100A: 3° 500A: 2.5° 600A: 2.5° |
Accuracy (1000A Range) | 1 to 20A: ?6% ± 0.1A 20A: 5% of Reading 50A: 3% of Reading 200A: 1.5% of Reading 1000A: 1% of Reading 1200A: 1% of Reading |
Phase Shift (1000A Range) | 20A: 5° 50A: 3° 200A: 1.5° 1000A: 1° 1200A: 1° |
Overload | 1200A for 30 min ON, 15 min OFF |
Frequency Range | 30Hz to 5kHz Current derating above 1kHz using the formula: 1000A x 1/F (in kHz) |
Load Impedance | 0.4? max |
Working/Common Mode Voltage | 600V Cat. III |
Output Termination | Jack |
What's included with the AEMC Instruments SR634
- AEMC SR634 AC Current Probe, 250, 500, 1200A AC