Accuenergy Acuvim IIBN-D-5A-P2 B ACnet Power/Energy Meter, LCD, 5 A/1 A input, 60 Vdc
$345.00
- Brand
- Accuenergy
- SKU:
- Acuvim IIBN-D-5A-P2
Accuenergy Acuvim IIBN-D-5A-P2 B ACnet Power/Energy Meter, LCD, 5 A/1 A input, 60 Vdc
Description:
Panel Mount; 5A/1A CT Input; 20-60Vdc Control Power
Track Specifications via Part Number:
Additional Informations:
Accuenergy Acuvim IIBN-D-5A-P2 Offers
The Accuenergy Acuvim IIBN has a built-in BACnet communication module specifically designed to monitor and collect real-time revenue-grade electrical data for building control and automation applications. This model includes the Acuvim IIBN basic unit with field selectable 1A or 5A current transformer input, 20 to 60V DC power supply, and an integrated mounting option with LCD display.
Features
- ANSI C12.20 Class 0.2 and IEC 62053-22 0.2s class revenue grade accuracy
- Built-in BACnet-IP protocol for integration with BAS and other monitoring and control systems
- Measures essential electrical system parameters in single element, two element and three element systems
- Directly measures up to 400Vl-n 690Vl-l without potential transformers
- Monitors all essential electrical system parameters in real-time
- Supports all types of CT from solid, split core and flexible Rogowski Coil, ideal for new and retrofit metering projects
- Secure access to meter via HTTPs encrypted webpage
Applications
The Acuvim IIBN is specially designed for these applications.
- Tenant Sub Metering
- Data Center Monitoring
- Building Automation
- Industrial Facility Metering
- Commercial Building Facility
Acuenergy Acuvim IIBN series Specifications
Current Inputs | Nominal Current | Channel 1 (5A), Channel 2 (1A), Channel 3 1A(333mV), Channel 4 1A(100mV Rope-CT), Channel 5 1A(80mA/100mA/200mA) |
Metering Range | Channel 1 (0~10A), Channel 2 (0~2A), Channel 3 (0~1.2A), Channel 4 (0~1.2A), Channel 5 (0~1.2A) |
Pickup Current | Channel 1 (5mA), Channel 2 (1mA), Channel 3 (5mA), Channel 4 (5mA), Channel 5 (5mA) |
Withstand | 20Arms Continuous, 0.1% of Nominal, 100Arms for 1 second, Non-Recurring |
Burden | 0.05VA (Typical) @ 5Arms |
Accuracy | 0.2% Full Scale |
Voltage Inputs | Nominal Full Scale | 400Vac L-N, 690Vac L-L (+20%) |
Withstand | 1500Vac Continuous, 2500Vac, 50/60Hz for 1 Minute |
Input Impedance | 2Mohm per Phase |
Metering Frequency | 45Hz~65Hz, 300Hz ~ 500Hz |
Pickup Voltage | 10Vac |
Accuracy | 0.2% Full Scale |
AC/DC Control Power | Operating Range | 100~415Vac, 50/60Hz; 100~300Vdc |
Burden | 5W |
Frequency | 50/60Hz |
Withstand | 3250Vac, 50/60Hz for 1 minute |
AC/DC Control Power | Operating Range | 100~415Vac, 50/60Hz; 100~300Vdc |
Burden | 5W |
Frequency | 50/60Hz |
Withstand | 3250Vac, 50/60Hz for 1 minute |
Operating Environment | Operation Temperature | - 40 to 85°C |
Relative Humidity | 5% to 95% Non-Condensing |